EasyManua.ls Logo

BENSHAW RSi H2 Series - Page 329

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Communications
317
890053-00-02
Comm.
Address
Parameter
Scale
Unit
Assigned content by bit
0h031B
Display the number
of poles for the 2nd
motor
-
-
Displays the number of poles for the
2nd motor
0h031C
Display the number
of poles for the
selected motor
-
-
Displays the number of poles for the
selected motor
0h031D
Select Hz/rpm
-
-
0: Hz, 1: rpm
0h031E
Reserved
-
-
-
0h031F
0h0320
Digital input
information
B15 B7
Reserved
B6
P7 (I/O board)
B5
P6 (I/O board)
B4
P5 (I/O board)
B3
P4 (I/O board)
B2
P3 (I/O board)
B1
P2 (I/O board)
B0
P1 (I/O board)
0h0321
Digital output
information
-
-
B15 B9
Reserved
B8-B6
Reserved
B5
Q1
B4
Relay 5
B3
Relay 4
B2
Relay 3
B1
Relay 2
B0
Relay 1
0h0322
Virtual digital input
information
-
-
B15 B8
Reserved
B7
Virtual DI 8 (COM-77)
B6
Virtual DI 7 (COM-76)
B5
Virtual DI 6 (COM-75)
B4
Virtual DI 5 (COM-74)
B3
Virtual DI 4 (COM-73)
B2
Virtual DI 3 (COM-72)
B1
Virtual DI 2 (COM-71)
B0
Virtual DI 1 (COM-70)
0h0323
Display the selected
motor
-
-
0: 1st motor/1: 2nd motor
0h0324
AI1
0.01
%
Analog input V1 or Thermal (I/O
board)
0h0325
AI2
0.01
%
Analog input V2 or I2 (I/O board)
0h0326
Reserved
-
-
Reserved
0h0327
Reserved
-
-
Reserved

Table of Contents