Parameter Lists
94
890053-00-02
4.2.7 Output Group (OUT)
Code
Name
LCD Display
Setting Range
Initial value
Property*
Ref.
00
Jump
Code
Jump Code
1-99
30
O
p.74
01
Analog
output1
AO1 Mode
0
Frequency
0
Frequency
O
p.179
1
Output Current
2
Output Voltage
3
DCLink Voltage
4
Output Power
7
Target Freq
8
Ramp Freq
9
PID Ref Value
10
PID Fdb Value
11
PID Output
12
Constant
02
Analog
output1
gain
AO1 Gain
-1000.0-1000.0 (%)
100.0
O
p.179
03
Analog
output1
bias
AO1 Bias
-100.0-100.0 (%)
0.0
O
p.179
04
Analog
output1
filter
AO1 Filter
010000 (msec)
5
O
p.179
05
Analog
constant
output1
AO1 Const
0.0-100.0 (%)
0.0
O
p.179
06
Analog
output1
monitor
AO1 Monitor
0.0-1000.0 (%)
0.0
X
p.179
07
Analog
output2
AO2 Mode
Identical to the OUT-01 (AO1 Mode)
selectoin range
0
Frequency
p.179
08
Analog
output2
gain
AO2 Gain
-1000.0-1000.0 (%)
100.0
O
p.179
09
Analog
output2
bias
AO2 Bias
-100.0-100.0 (%)
0.0
O
p.179
10
Analog
output2
filter
AO2 Filter
010000 (msec)
5
O
p.179
11
Analog
constant
output2
AO2 Const
0.0-100.0 (%)
0.0
O
p.179
12
Analog
output2
monitor
AO2 Monitor
0.0-1000.0 (%)
0.0
X
p.179
30
Fault
output
item
Trip OutMode
bit
000-111
010
O
p.187
Bit 0
Low voltage
Bit 1
Any faults other than low voltage
Bit 2
Automatic restart final failure
31
Multi-
function
relay1
Relay 1
0
None
23
Trip
O
p.183
32
Multi-
function
relay2
Relay 2
1
FDT-1
14
RUN
33
Multi-
function
relay3
Relay 3
2
FDT-2
0
None
34
Multi-
function
relay4
Relay 4
3
FDT-3
0
None
35
Multi-
function
relay5
Relay 5
4
FDT-4
0
None
36
Multi-
function 1
item
Q1 Define
5
Over Load
0
None
bit 2 bit 1 bit 0
1 1 1
0 0 0

Table of Contents