10.3.6 Modbus-RTU Protocol
10.3.6.1 Function Code and Protocol
In the following section, station ID is the value set at COM-01 (Int485 St ID), and the starting
address is the communication address (starting address size is in bytes). For more information
about communication addresses, refer to 10.3.7 Compatible Common Area Parameter on page
311.
Reading up to 8 Consecutive Inverter Parameters Based on the Set Number - Read Holding
Register (Func. Code: 0x03) and Read Input Register (Func. Code: 0x04)
Read Holding Registers (Func. Code: 0x03) and Read Input Registers (Func. Code: 0x04) are
processed identically by the inverter.