Communications
309
890053-00-02
10.3.6.1.3 Error Response
Slave Station ID
Func. Code
Except. Code
CRC(Lo)
CRC(Hi)
1 byte
1 byte
1 byte
1 byte
1 byte
* Func. Code of the error response is [Request Func. Code] + 0x80.
10.3.6.1.4 Writing One Inverter Parameter Value (Func. Code: 0x06)
Codes
Description
Addr.
Address 1 of the inverter parameter (common area or keypad) to be written to.
Reg. Value
The inverter parameter (common area or keypad) value to write with.
Except. Code
Error codes
10.3.6.1.5 Request
Slave
Station
ID
Func.Code
Addr (Hi)
Addr(Lo)
Value(Hi)
Value(Lo)
CRC(Lo)
CRC(Hi)
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
10.3.6.1.6 Normal Response
Slave
Station
ID
Func.Code
Addr (Hi)
Addr(Lo)
Value(Hi)
Value(Lo)
CRC(Lo)
CRC(Hi)
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
1 byte
10.3.6.1.7 Error Response
Slave Station ID
Func. Code
Except. Code
CRC(Lo)
CRC (Hi)
1 byte
1 byte
1 byte
1 byte
1 byte
* Func. Code of the error response is [Request Func. Code] + 0x80.
10.3.6.1.8 Writing Multiple Registers (Func. Code: 0x10)
Codes
Description
Start Addr.
Starting address 1 of the inverter parameters (common area or keypad) to
be written to.
No. of Reg.
Number of the inverter parameters (common area or keypad) to be written.
Reg. Value
The inverter parameter (common area or keypad) values to write with.
Except. Code
Error codes

Table of Contents