5.4 Advance Group (ADV)
5.4.1 ADV-01 Acc/Dec Pattern Configuration
A Linear Accel and Decel pattern features a linear increase (and decrease) of the output
frequency at a fixed rate. An S-curve pattern provides a smoother and more gradual increase
(and/or decrease) of output frequency. Acc/Dec slope patterns can be configured to enhance and
smooth the inverter’s acceleration and deceleration curves. An S-curve can be set with ADV-01
(accel) and ADV-02 (decel) and slope can be adjusted using ADV-03 ~ ADV-06.
S-curve Acc start
gradient
S-curve Dec start
gradient
Acc/Dec Pattern Setting Details
ADV-03 sets the slope at the start of the acceleration curve. The set
percentage applies to 50% below the first half of the total acceleration
curve. When the frequency reference is set at 60 Hz and ADV-03 is set
to 50%, S-Curve acceleration will be applied to 0–15 Hz. (50% below half
the reference frequency). Linear acceleration will be applied to the 15-30
Hz. section.
ADV-04 sets the slope at the end of the acceleration curve. The set
percentage applies to the second half of the total acceleration curve
where operating frequency is reaching the reference frequency. When
the reference frequency is 60 Hz. and ADV-04 is set to 50%, S-Curve
acceleration will be applied to 45-60 Hz. (50% above half the reference
frequency). Linear acceleration will be applied to the 30~45 Hz. section.
Sets the slope at the start of S-curve deceleration. S-Curve
deceleration is applied to the portion of the deceleration curve that is
50% above half the reference frequency (60-45 Hz.). Same as S-Curve
End acceleration.
Sets the slope at the end of S-curve deceleration. S-Curve
deceleration is applied to the portion of the deceleration curve that is
50% below half the reference frequency (15-0 Hz.). Same as S-Curve
start acceleration.