Acc/Dec Time Setup via Multi-function Terminals – Setting Details
Set multi-step acceleration time1–7.
Set multi-step deceleration time1–7.
IN-65~71
Px Define (P1~P7)
Choose and configure the terminals to use for multi-step Acc/Dec time
inputs
Acc/Dec commands are recognized as binary code inputs and will control the
acceleration and deceleration based on parameter values set with BAS-70–
82 and BAS-71–83.
Example: The P6 and P7 terminals are set as XCEL-L and XCEL- M
respectively, the following operation will be available.
[Multi-function terminal P6, P7 configuration]
Set the time for the inverter to check for other terminal block inputs. If IN-89 is
set to 100 ms and a signal is supplied to the P6 terminal, the inverter
searches for other inputs over the next 100 ms. When the time expires, the
Acc/Dec time will be set based on the input received at P6.