Parameter Descriptions
136
890053-00-02
5.3.3.6 BAS-70 Multi-step Acc/Dec Time Configuration
Digital input terminals can be configured for different Acc and Dec times. Up to 7 acceleration
times and 7 deceleration times can be set. Choose (up to 3) digital input terminals (P1 ~ P7) and
set the corresponding parameters (IN-65~IN-71) to 11 (XCEL-L), 12 (XCEL-M) and 13 (XCEL-H).
These are recognized as binary inputs (000 ~ 111). Acc times and Dec times are set with BAS-70
through BAS-83.
Group
Code
Name
LCD Display
Parameter Setting
Setting
Range
Unit
DRV
03
Acceleration
time
Acc Time
20.0
240V:7.5~60HP
0.0600.0
sec
480V,575V:
7.5~125HP
60.0
240V: 75~125HP
480V: 150~400HP
100.0
480V: 500~800HP
04
Deceleration
time
Dec Time
30.0
240V: 7.5~60HP
0.0600.0
sec
480V,575V:
7.5~125HP
90.0
240V: 75~125HP
480V: 150~400HP
150.0
480V: 500~800HP
BAS
70~83
Multi-step
Acceleration/
Deceleration
time17
Acc Time 17
x.xx secs
0.0600.0
sec
Dec Time 17
x.xx secs
0.0600.0
sec
IN
65~71
Px terminal
configuration
Px Define (Px:
P1P7)
11
XCEL-L
042
-
12
XCEL-M
13
XCEL-H
89
Multi-step
command delay
time
In Check Time
1
15000
ms