Set a time interval for the inverter to check for additional terminal block
inputs after receiving an input signal.
After adjusting IN-89 to 100 ms and an input signal is received at P6, the
inverter will search for inputs at other terminals for 100 ms, before
proceeding to accelerate or decelerate based on the configuration at P6.
5.3.3.5 BAS-69 Configuring Acc/Dec Time - Switch Frequency
Set a switch frequency (BAS-69) to switch between 2 different Accel times and 2 different Decel
times. Parameters BAS-70 (step accel time1) and BAS-71 (step decel time1) are in effect below
the switch frequency. Parameters DRV-03 (Accel time) and DRV-04 (Decel time) are in effect
above the switch frequency.
Multi-step
acceleration time1
Multi-step
deceleration time1
Acc/Dec time
switch frequency
Acc/Dec Time Switch Frequency Setting Details
Set the Acc/Dec transition frequency (BAS-69). Acc/Dec slopes configured at
BAS-70 and BAS-71 will be used when the inverter’s operating frequency is
at or below the switch frequency. When the operating frequency exceeds the
switch frequency, Acc/Dec slopes configured at DRV-03 and DRV-04 will be
used. Multi-step digital inputs (XCEL-L, XCEL-M, XCEL-H) override the BAS-
69 settings. The ‘Xcel Change Fr’ parameter is applied only when ADV-24 (Freq
Limit Mode) is set to ‘NO’.