Parameter Descriptions
134
890053-00-02
5.3.3.4 BAS-50 Multi-step Frequencies (Fixed Speed Inputs)
Multi-step operations (Fixed Speed Inputs) can be assigned to the Px terminals. Seven steps (1
through 7) can be configured using (3) digital input terminals. Step 0 uses the frequency reference
source set with DRV-07. Set Px terminals to 7 (Speed-L), 8 (Speed-M) and 9 (Speed-H). These are
recognized as binary inputs (000 ~ 111) and work in combination with Fx or Rx run commands. The
inverter operates according to the frequencies set with parameters BAS-5056 and the binary
command combinations.
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
BAS
50~56
Multi-step
frequency 17
Step Freq - 17
10.00~60.00 Hz.
0.00, Low
Freq High Freq*
Hz
IN
65~71
Px terminal
configuration
Px Define
(Px: P1~P7)
7
Speed-L
042
-
8
Speed-M
-
9
Speed-H
-
89
Multi-step
command delay
time
InCheck Time
1
15000
ms
Multi-step Frequency Setting Details
Code
Description
BAS-50 ~ 56
Configure multi-step frequencies 1~7.
IN-65~71
Px
Define
Choose the terminals to setup as multi-step inputs. Set the relevant
parameters (IN-6571) to 7 (Speed-L), 8 (Speed-M), or 9 (Speed-H).
Example below using terminals P5, P6, and P7 have been set to Speed-L,
Speed- M and Speed-H respectively (default settings). The following multi-
step operation will be available.
Speed
Fx/Rx
P7
P6
P5
0
-
-
-
1
-
-
2
-
-
3
-
4
-
-
5
-
6
-
7