5.3.3.4 BAS-50 Multi-step Frequencies (Fixed Speed Inputs)
Multi-step operations (Fixed Speed Inputs) can be assigned to the Px terminals. Seven steps (1
through 7) can be configured using (3) digital input terminals. Step 0 uses the frequency reference
source set with DRV-07. Set Px terminals to 7 (Speed-L), 8 (Speed-M) and 9 (Speed-H). These are
recognized as binary inputs (000 ~ 111) and work in combination with Fx or Rx run commands. The
inverter operates according to the frequencies set with parameters BAS-50–56 and the binary
command combinations.
0.00, Low
Freq– High Freq*
Px terminal
configuration
Multi-step
command delay
time
Multi-step Frequency Setting Details
Configure multi-step frequencies 1~7.
Choose the terminals to setup as multi-step inputs. Set the relevant
parameters (IN-65–71) to 7 (Speed-L), 8 (Speed-M), or 9 (Speed-H).
Example below using terminals P5, P6, and P7 have been set to Speed-L,
Speed- M and Speed-H respectively (default settings). The following multi-
step operation will be available.