[External Trip]
5.6.4.4 BX, Output Block
Set one of the digital input terminals (P1 ~ P7) to ‘5 (BX)’. When activated, the inverter output is
blocked, and operation stops. The LCD displays ‘BX”. The “HAND” button is also disabled. The
BX input is not a latched fault. When the digital input is deactivated, operation resumes.
Px terminal setting
options
Output Block by Multi-function Terminal Setting Details
When the operation of the digital input terminal is set to ‘5 (BX)’ and is activated
during operation, the inverter blocks the output and ‘BX’ is displayed on the
keypad display. While ‘BX’ is displayed on the keypad screen, the inverter’s
operation information including the operation frequency and current at the time of
the BX signal can be viewed but is not recorded in the TRP group (fault history).
The inverter resumes operation when the BX terminal deactivated with the run
command still applied.
5.6.4.5 JOG operation
The jog operation allows for temporary control of the inverter. There are two was to apply a jog
and start command using the digital input terminals.
•
Jog-1 using a digital input terminal set to JOG along with a start command (Fx or Rx).
•
Jog-2 using a single digital input set to FWD JOG or REV JOG.
5.6.4.5.1 Jog Operation 1-Forward Jog by Multi-function Terminal
The jog operation is available in the forward (or reverse) direction, using two input terminals (Fx
and JOG). The table below lists parameter settings for a forward jog operation with a separate
Run (Fx) command.