Configures the slope and off-set values of the output frequency based
on a mA input at the I2 terminal.
5.1.4.4.2 IN-35 Setting a Frequency Reference for 0-10V Input (I2 Terminal)
You can modify the frequency reference using a voltage input at the I2 terminal. First with SW4, select V2
(right) for the voltage input. Set DRV-07 (Frequency reference source) to ‘4 (V2)’ and apply 0–12V input
voltage to the I2 terminal. Scaling of the input voltage is done with IN-38 ~ IN-41. View the input voltage at IN-
35. Parameters for voltage input (IN-35–47) will only be displayed when I2 is set to receive a voltage
input (DRV-07 is set to ‘4’ (V2)).