Parameter Descriptions
114
890053-00-02
IN-53 I2 Curr x1
IN-54 I2 Perc y1
IN-55 I2 Curr x2
IN-56 I2 Perc y2
Configures the slope and off-set values of the output frequency based
on a mA input at the I2 terminal.
5.1.4.4.2 IN-35 Setting a Frequency Reference for 0-10V Input (I2 Terminal)
You can modify the frequency reference using a voltage input at the I2 terminal. First with SW4, select V2
(right) for the voltage input. Set DRV-07 (Frequency reference source) to ‘4 (V2) and apply 012V input
voltage to the I2 terminal. Scaling of the input voltage is done with IN-38 ~ IN-41. View the input voltage at IN-
35. Parameters for voltage input (IN-3547) will only be displayed when I2 is set to receive a voltage
input (DRV-07 is set to ‘4’ (V2)).
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
07
Frequency
reference source
Freq Ref Src
4
V2
011
-
IN
35
V2 input display
V2 Monitor
0.00
0.0012.00
V
37
V2 input filter time
constant
V2 Filter
10
010000
msec
38
Minimum V2 input
voltage
V2 Volt x1
0.00
0.0010.00
V
39
Output % at
minimum V2
voltage
V2 Perc y1
0.00
0.00100.00
%
40
Maximum V2 input
voltage
V2 Volt x2
10.00
0.0010.00
V
41
Output % at
maximum V2
voltage
V2 Perc y2
100.00
0.00100.00
%
46
Invert V2 rotational
direction
V2 Inverting
0
No
01
-
47
V2 quantizing level
V2
Quantizing
0.04
0.00*, 0.04
10.00
%
Quantizing is disabled if ‘0’ is selected.