5.1.4.5 IN-91 TI Terminal (Pulse) as the Frequency Reference Source
You can modify the frequency reference using a pulsed frequency input at the TI terminal. Set DRV-07
(Frequency reference source) to ‘9 (Pulse)’ and apply a 0–32 kHz. input to TI. Scaling of the pulsed
input is done with IN-93 ~ IN-96. View the pulsed input at IN-91. Parameters for a pulse input (IN-91–
98) will only be displayed when TI is set to receive a pulsed input (DRV-07 is set to ‘9’ (Pulse)).
Frequency
reference source
Frequency at
maximum analog
input
TI input filter time
constant
Output% at TI
minimum pulse
Output% at TI
maximum pulse
Invert TI direction of
rotation
*Quantizing is disabled if ‘0’ is selected.
TI Pulse Input Setting Details
Configures the frequency reference at the maximum pulse input. The
frequency reference is based on 100% of the value set with IN-96.
•
If IN-01 is set to 40.00 and parameters IN-93–96 are set at default,
32 kHz input to TI yields a frequency reference of 40.00 Hz.
•
If IN-96 is set to 50.00 and parameters IN-01, IN-93–95 are set at
default, 32 kHz input to the TI terminal yields a frequency reference
of 30.00 Hz.
Displays the pulse frequency supplied at TI.
Sets the time for the pulse input at TI to reach 63% of its nominal
frequency (when the pulse frequency is supplied in multiple steps).