Parameter Descriptions
111
890053-00-02
5.1.4.3.2 IN-12 Setting a Frequency Reference for -10+10V Input
Set DRV-07 (Frequency reference source) to ‘2 (V1)’, and then set IN- 06 (V1 Polarity) to ‘1 (bipolar)’.
Use the output voltage from an external source to provide a bipolar input to V1.
V1 terminal wiring
Group
Code
Name
LCD Display
Parameter
Setting
Setting Range
Unit
DRV
07
Frequency reference
source
Freq Ref Src
2
V1
011
-
IN
01
Frequency at maximum
analog input
Freq at 100%
60.00
0 Max
Frequency
Hz
05
V1 input monitor
V1 Monitor
0.00
-12.0012.00
V
V
06
V1 polarity options
V1 Polarity
1
Bipolar
01
-
12
V1 minimum input
voltage
V1- volt x1
0.00
-10.000.00 V
V
13
V1 output at minimum
voltage (%)
V1- Perc y1
0.00
-100.00
0.00%
%
14
V1 maximum input
voltage
V1- Volt x2
-10.00
-12.00 0.00
V
V
15
V1 output at maximum
voltage (%)
V1- Perc y2
-100.00
-100.00
0.00%
%