Parameter Descriptions
112
890053-00-02
Rotational Directions for Different Voltage Inputs
Command /
Voltage Input
Input voltage
0+10 V
-100 V
FWD
Forward
Reverse
REV
Reverse
Forward
-1010 V Voltage Input Setting Details
Code
Description
IN-12 V1- Volt x1
IN-13 V1 Perc y1
IN-14 V1 Volt x2
IN-15 V1- Perc y2
These parameters are used to set the slope and offset value of the
output frequency based on a frequency reference with a negative input
voltage. These parameters are displayed only when IN-06 is set to ‘1
(bipolar).
As an example, if the minimum input voltage (at V1) is set to -2 (V) with
10% output ratio, and the maximum voltage is set to -8 (V) with 80%
output ratio respectively, the output frequency will vary within the range
of 648 Hz.
For details about the 0+10 V analog inputs, refer to the code
descriptions IN-08 (V1 volt x1) IN-11 (V1 Perc y2) on page 108.