5.1.4.3 IN-05 V1 Terminal as the Frequency Reference Source
You can set and modify a frequency reference by applying voltage inputs to the V1 terminal. Use
voltage inputs ranging from 0–10 V (unipolar) for forward only operation. Also, voltage inputs ranging
from -10 to +10 V (bipolar) can be applied for both directions, where negative voltage inputs are used in
reverse operations.
5.1.4.3.1 Setting a Frequency Reference for 0–10 V Input
Set IN-06 (V1 Polarity) to ‘0 (unipolar)’. Use a voltage output from an external source or use the
voltage output from the VR terminal to provide inputs to V1. Refer to the diagrams below for the wiring
required for each application.