Parameter Descriptions
109
890053-00-02
010 V Input Voltage Setting Details
Code
Description
IN-01
Freq at 100%
Configures the frequency reference at the maximum input voltage when a
potentiometer is connected to the control terminal block. A frequency set
with parameter IN-01 becomes the maximum frequency only if the value set in
parameter IN-11 (or IN-15) is 100 (%).
Set parameter IN-01 to 60.00 and use default values for parameters IN-
05IN-
16.
Motor will run at 60.00 Hz when a 10 V input is provided at V1.
Set parameter IN-11 to 50.00 (%) and use default values for parameters
IN-01IN-
16.
Motor will run at 30.00 Hz (50% of the default maximum frequency 60
Hz) when a 10 V input is provided at V1.
IN-05
V1 Monitor[V]
Monitors the input voltage at V1.
IN-07
V1 Filter
V1 Filter may be used when there are large variations in the applied reference
frequency (noise filter). Variations can be mitigated by increasing the time
constant, but this will delay the response time when changing the reference
frequency. The value t (time) indicates the time required for the frequency to
reach 63% of the reference, when external input voltages are provided in
multiple steps.
IN-08 V1 Volt x1
IN-09 V1 Perc y1
IN-10 V1 Volt x2
IN-11 V1 Perc y2
These parameters are used to configure the slope and offset values of the
Output Frequency based on a frequency reference of Input Voltage.