Parameter Descriptions
194
890053-00-02
[Example of auto restart with PRT-09 setting of 2]
Normally when a fault occurs, the inverter cuts off the output and the motor will free run. Another fault
may be triggered if the inverter begins its operation while motor load is in a free-run state.
When auto reset/restart is enabled and a run command applied, the inverter will reset from
a fault and the motor will automatically start to rotate.
Note
Using Speed Search: See CON-71~ CON-75. During Auto reset/restart, a fault may be
triggered when the inverter restarts into a spinning load. To prevent faults, set speed
search CON-71, bit 1 to “ON” (set to 1). The inverter will perform a speed search after a
fault reset.
In HAND mode, the auto restart resets the trip but does not restart the inverter.