Parameter Descriptions
188
890053-00-02
Fault Output by Multi-function Output Terminal and Relay - Setting Details
Code
Description
OUT-30
Trip Out Mode
Setting
Function
Bit2
Bit1
Bit0
Operates when low voltage faults occur
Operates when faults other than low voltage
occur
Operates when auto restart fails (PRT-08,
PRT-09)
LCD bit representation in parameter view. When the top segment is
black, bit is set to "ON".
Item
Bit Status (On)
Bit Status (Off)
LCD Display
bit 2
bit 1
bit 0
1
1
1
0
0
0
OUT-31~OUT-35
Relay1~Relay5
Configure Relay1~ Relay5 output function. Set OUT-31~35 (Relay1-
Relay5) to ‘23 (Trip)’. When a fault occurs, the output will be activated.
OUT-36
Q1 Define
Configure the open collector output (Q1) to ‘23 (Trip). When a fault
occurs, the output will be activated.
OUT-53
TripOut On Dly,
OUT-54
TripOut OffDly
When a trip occurs, the relays will be activated after the delay time set
in OUT-53 (On Dly). After a reset, the relays will be initialized after the
delay time set in OUT-54 (Off Dly).