Changing DRV-06 (Cmd Source) to Keypad
The AUTO button is now the start and stop command for the inverter.
Pressing the AUTO button once puts the inverter in Ready mode (AUTO LED blinking).
Pressing the AUTO button a second time, will start the inverter.
• From the OFF state, pressing the AUTO button once (Green LED blinking) puts inverter in
Ready mode.
• Pressing the AUTO button a second time, starts the inverter.
• Pressing the AUTO button while running, stops the inverter.
• Pressing the OFF button also stops the inverter.
• The speed (frequency) is still Keypad-1 and can be set at the Monitor display (MON).
Frequency is on Line-1.
o Pressing the PROG/ENT button
o Use the Up, Down, Left and Right arrow buttons.
o Press the PROG/ENT button again to save the change.
o The inverter will go to the newly programmed speed.
• Other remote Frequency References (DRV-07) may be used.
• In Auto mode, the frequency (speed) displayed at the Monitor display (MON) is duplicating
parameter DRV-01 (Cmd Frequency). The default speed is 0 Hz.
Changing DRV-07 (Freq Ref Src)
DRV-07 - Keypad-1 vs Keypad-2
When changing speed (frequency) at the Keypad in AUTO mode, the difference between Keypad-1
and Keyypad-2 settings is:
• Both - Still have to press the PROG/ENT button to change the speed.
• Use the Up, Down, Left and Right arrow buttons to change the speed.
• Keypad-1 - Press the PROG/ENT button again to save the newly set speed. The inverter will
go to the newly programmed speed.
• Keypad-2 - The speed is changing while setting the new speed.
DRV-07 - Other Frequency Reference Sources
When setting DRV-07 to the other frequency refernce sources listed below, the inverter simply looks
at the designated terminal for the frequency reference signal.
Choices are:
• Analog: V1, V2, I2 and with Ext IO Bd. V3, I3
• Communications: Int 485 (Modbus)
• Field bus: Other Communication Option Cards
• Pulse: High Frequency signal
OFF Button
The OFF button puts the inverter in the OFF Mode, Red LED on solid. It will not start until put in HAND
mode or AUTO mode with a remote start command. Note: A Fire mode input can be applied and is
active in the OFF mode.