13
Preparing the Installation
890053-00-02
If you are installing multiple inverters of different ratings, provide sufficient clearance to meet the
clearance specifications of the larger inverter. The H2 inverters rated up to 30 kW may be installed
side-by-side.
NOTE
The vent covers must be removed for side-by-side installations.
Side-by-side installation cannot be used for the H2 inverters rated for 37 kW and above.
For the H2 inverters rated for 50 HP (37 kW) and above, if the installation site satisfies the
UL Open Type requirements and there is no danger of foreign objects getting inside the
inverter, the vent cover may be removed to improve cooling efficiency.