Parameter Lists
91
890053-00-02
Code
Name
LCD Display
Setting Range
Initial value
Prop
*
Ref.
150~800HP
130.0
575V only
79
Energy buffering stop level
KEB Stop Lev
CON-78 ~ 145.0 (%)
130.0
240V, 480V:
7.5~125HP
Δ
125.0
480V:
150~800HP
135.0
575V only
80
Energy buffering slip gain
KEB Slip Gain
0-20000
300
240V:7.5~40HP
O
480V:
7.5~800HP
100
240V: 50~125HP
25
575V
81
Energy buffering P-Gain
KEB P-Gain
0-20000
1000
240V:7.5~40HP
O
480V:
7.5~800HP
1800
240V: 50~125HP
3000
575V: 7.5~50HP
1500
575V: 60~125HP
82
Energy buffering I-Gain
KEB I-Gain
1-20000
500
240V:7.5~40HP
O
480V:
7.5~800HP
200
240V: 50~125HP
575V
83
Energy buffering acceleration
time
KEB Acc Time
0.0-600.0 sec
10.0
240V, 480V:
7.5~125HP
O
30.0
480V:
150~800HP
5.0
575V
85
9
Flux estimator proportional
gain 1
Flux P Gain 1
100 - 700
370
230V, 460V
I
p.239
0-500
170
575V
86
Flux estimator proportional
gain 2
Flux P Gain 2
0 - 100
0
230V, 460V
I
p.239
70-120
90
575V
87
Flux estimator proportional
gain 3
Flux P Gain 3
0 - 500
100
I
88
Flux estimator integral gain 1
Flux I Gain 1
0 - 200
50
230V, 460V
I
80
575V
89
Flux estimator integral gain 2
Flux I Gain 2
0 - 200
50
I
90
Flux estimator integral gain 3
Flux I Gain 3
0 - 200
50
I
91
Sensorless voltage
compensation 1
SL Volt Comp 1
0 - 60
35
230V, 460V
I
p.239
60-400
110
575V
92
Sensorless voltage
compensation 2
SL Volt Comp 2
0 - 60
20
230V, 460V
I
0-400
110
575V
93
Sensorless voltage
compensation 3
SL Volt Comp 3
0 - 60
20
I
94
Sensorless field weakening
start frequency
SL FW Freq
0 - 110%
100
I
p.239
95
Sensorless gain switching
frequency
SL Fc Freq
0.00 - 8.00 Hz
2.00
I
97
Sensorless Slip
Compensation1
SL Slip Comp1
0-200
100 (575V only)
I
p.239
98
Sensorless Slip
Compensation2
SL Slip Comp2
0-200
50 (575V only)
I
[1] CON-09 is displayed when DRV-09 is set to '3' (IM Sensorless). Does not apply to 240V, 30~125 HP Inverters.
[3] CON-24 - 33 and CON-52 - 57 are displayed when DRV-09 is set to '3' (IM Sensorless). Does not apply to 240V, 30~125 HP
Inverters. CON-52 - 57 are displayed when DRV-09 is set to '4' (PM Sensorless). Does not apply to 240V, 30~125 HP, 480V, 150~800
HP and all 575V Inverters.
[4] When ADV.74 is set to Yes, defaults change to 150%.
[5] CON-34 - 47 and CON-69 are displayed when DRV-09 is set to '4' (PM Sensorless). Does not apply to 240V, 30~125 HP, 480V,
150~800 HP and all 575V Inverters.
[6] CON-72 is displayed after Flying Start-1 and when any CON-71 bit is set to ‘1’.
[7] CON-7375 are displayed when any CON-71 bit is set to ‘1’.
[8] CON-7883 are displayed when CON-77 is set to ‘1 (Yes)’.
[9] CON-85 ~ 95 are displayed when DRV-09 is set to '3' IM Sensorless. Does not apply to 240V, 30~125 HP Inverters.
[10] PM Sensorless: Does not apply to 240V, 30~125 HP, 480V, 150~800 HP and all 575V Inverters.