Parameter Descriptions
132
890053-00-02
5.3.3.2 Square Reduction V/F Pattern Operation
Square reduction V/F pattern is ideal for variable torque loads such as fans and pumps that do not
require high torque at frequencies lower than the base frequency. The inverter provides a non-
linear V/F acceleration and deceleration pattern to sustain enough torque throughout the speed
range.
Group
Code
Name
LCD Display
Parameter Setting
Setting Range
Unit
BAS
07
V/F pattern
V/F Pattern
1
Square
03
-
3
Square2
Square Reduction V/F pattern Operation - Setting Details
Code
Description
BAS-07 V/F
Pattern
Sets the parameter value to 1 (Square)’ or ‘2 (Square2)’ according to the
load’s start characteristics.
Setting
Function
1
Square
The inverter produces output voltage proportional to 1.5
square of the operating frequency.
3
Square2
The inverter produces output voltage proportional to 2
square of the operating frequency. This setup is ideal for
variable torque loads such as fans or pumps.

Table of Contents