Pulse output TO and multi-function output Q1 share the same terminal. Set
OUT-36 to ‘38’, TO for a 0-32kHz pulsed output at Q1 terminal.
When connecting the pulse signal between the inverters, connect pulse output
(Q1/TO-EG) to pulse input (TI-CM) directly.
The Gain and Bias settings provide scaling adjustment of the pulse output
signal. The graphs below illustrate adjustments of OUT-62 (TO Gain) and OUT-
63 (TO Bias) percentages and the effect on the pulse output signal (TO). The X-
axis is the % value of the selected output item and the Y-axis is the
corresponding frequency (0–32kHz) at the Q1/TO terminal.
For example, if the maximum frequency set with DRV-20 (Max Freq) is 60Hz
and present output frequency is 30Hz, then the x-axis value on the next graph is
50%.
The frequency output is based on the following equation: