Parameter Descriptions
206
890053-00-02
Code
Description
mode does not increase the count value at PRT-48
(Fire Mode Cnt).
PRT-46
Fire Mode Dir
Sets the run direction for Fire mode operation.
PRT-47
Fire Mode Freq
Sets the operation frequency for Fire mode.
PRT-48
Fire Mode Cnt
Counts the number of the Fire mode operations. The number increases
only when PRT-45 (Fire Mode Sel) is set to ‘Fire Mode. The count
increases up to 99, then it does not increase any more. Does not
increase the count during Fire Mode testing.
If damper or lubrication operations are set for the inverter, Fire mode operation is performed after
the delay times set in the relevant operations. Note that Fire mode operation voids the
product warranty.
In Fire mode test mode, the inverter does not ignore the faults or perform a reset restart. All
the faults will be processed normally. Fire mode test mode does not increase the Fire mode
count (PRT-48). When the Fire mode operation is complete, the inverter stops operating and is
turned off.