-10-10 V input voltage terminal
If the analog voltage/current input terminal selection switch
(SW4) at the terminal block is set to I (current), input 0-20
mA current. If it is set to V (voltage), input 0–10 V
Communication command via a communication option card
TI Pulse input terminal (0-32 kHz Pulse input)
Selects the external input source to be used as an auxiliary feedback source
for PID control. When the external input source is selected, the reference is
determined using the input value at the source (set at PID-10) and the value
set at PID-13 PID Ref1AuxMod.
-10-10 V input voltage terminal
When the analog voltage/current input terminal selection
switch (SW4) at the terminal block is set to I (current), input
0-20 mA current. If it is set to V (voltage), input 0–10 V
TI Pulse input terminal (0-32 kHz Pulse input)
Communication command via a communication option card
The PID-22 (PID Fdb AuxMod) provides formulas to calculate the final
feedback value (PID-20 and PID-21). If PID-21 (PID Fdb AuxSrc) is set to any
other value than ‘None,’ the final feedback is calculated using the input values
at the two feedback sources (set at PID-20 and PID-21).
M= Value by the Feedback Src set at PID-20
G= Gain value set at PID-23
A= Value by the feedback auxiliary source set at PID-21
Gain value used in a formula set at PID-22.
Sets the maximum and minimum value by adding or subtracting the PID Fdb
Band value (PID-24) from the reference value. When the feedback value is
between the maximum and minimum value, this parameter maintains the PID
output.