Application Groups
271
890053-00-02
Time Event Function Setting Details
Code
Description
AP3-01 Now Date
AP3-02 Now Time
AP3-03 Now Weekday
Sets the current date, time, and day of the week. The Time Event function
is based on the setting. When the user sets the summer time start date, the
current time is subtracted by one hour. ex) [AP3- 04 Summer T Start] is set to
April 1, and if it is 1:59 on April 1, it will not be 2:00 a minute later and it will
be 1:00 on April 1. If [AP3-05 Summer T Stop] is set to December 25th,
then it will be 1:59 on December 25th, and it will be 3:00 on December 25
instead of 2:00 a minute later. Summer time is different for each country. The
parameter is based on 2 o'clock. If there is no charge on the RTC battery, it
is initialized to 00:00 on January 1, 2000 when the inverter power is off / on.
AP3-04 Summer T Start
AP3-05 Summer T Stop
Set the Summer time start and finish date.
AP3-06 Date format
Select the desired date format.
Configuration
Function
0
YYYY/MM/DD
Year/Month/Day is displayed.
1
MM/DD/YYYY
Month/Day/Year is displayed (USA).
2
DD/MM/YYYY
The format of Day/Month/Year is displayed
(Europe).
AP3-10 Period Status
Bits 0–3 are used to indicate the time module that is currently in use among
the 4 different time modules set at AP3-11–AP3-22.
Bits 411 are used to indicate the exception day that is set at AP3- 30AP3-
53.
AP3-11AP3-20
Period 1–4 Start T
The start time for the 4 time periods can be set up to 4.
AP3-12AP3-21
Period 1–4 Stop T
The end time for the 4 time periods can be set up to 4.
AP3-13AP3-22
Period 1~4 Day
The Time period date for the operation can be set up to 4. It can be set on a
weekly basis. If the bit is ‘1 (on)’, it indicates the relevant day is selected. If
the Bit is ‘0 (off)’, it indicates the relevant day is
not selected.
Bit
6
5
4
3
2
1
0
Sunday
Monday
Tuesday
Wednesday
Thursday
Friday
Saturday
AP3-30AP3-51
Exception18 Start T
The operation start time for the 8 Exception days can be set.
AP3-31AP3-52
Exception18 Stop T
The operation end time for the 8 Exception days can be set.
AP3-32AP3-53
Exception18 Date
The date for the 8 Exception days can be set.
AP3-70
Time Event En
Enables or disables the Time Event
Setting
Function
0
No
Time Event is not used.
1
Yes
Time Event is used.
AP3-71
T-Event Status
It shows which T-Event from 1–8 is being performed.
7
6
5
4
3
2
1
0
T-Event 8
T-Event 7
T-Event 6
T-Event 5
T-Event 4
T-Event 3
T-Event 2
T-Event 1
AP3-7286
T-Event1–8 Period
Select the desired module of the Time Module and Exception Day set in
AP3-11AP3-53 for the relevant events.
If the bit is 1, it indicates the relevant Time Module or Exception Day is
selected. If the Bit is 0, it indicates the Time Module or Exception Day is not