Application Groups
273
890053-00-02
Time Period Parameter Setting
There are 4 Time Period Sets in the Time Event. Each Time Period Set has:
Period 14 Start (Start time), Period 14 Stop T (End time), and Period 14 Day (Operation day)
for which they can be set.
Time Period
Schedule
Time Period 1
Every Sunday, Monday, Wednesday, Thursday, and Friday at 06: 00 (On) and 18:
00 (Off)
Time Schedule
Code
Function
Setting
AP3-11
Period1 StartT
06: 00
AP3-12
Period1 StopT
18: 00
AP3-13
Period1 Day
1101110
Time Period 2
Every Sunday and Saturday for 24 hours (On)
Time Schedule
Code
Function
Setting
AP3-14
Period2 StartT
00: 00
AP3-15
Period2 StopT
24: 00
AP3-16
Period2 Day
1000001
Time Period 3
Every Sunday, Thursday, Friday, and Saturday at 10: 00 (On) and 14: 00 (Off)
Time Schedule
Code
Function
Setting
AP3-17
Period3 StartT
10: 00
AP3-18
Period3 StopT
14: 00
AP3-19
Period3 Day
1000111
The tables above show the parameter values for Time Period 1, Time Period 2, and Time Period 3.
When the parameters are set for the Time Periods 1-3, this indicates the Time Event function turns on
and off on the following days and time.
<Time Period setting Time Chart>