EasyManua.ls Logo

BENSHAW RSi H2 Series - Trip Mode (TRP)

BENSHAW RSi H2 Series
397 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
LCD Display Modes
285
890053-00-02
MC1 ---> Pump
62
PRT
14
Lost Preset F
0.00
Hz
63
PRT
15
AI Lost Level
0
Half of x1
64
PRT
20
OL Trip Select
1
Free-Run
65
PRT
21
OL Trip Level
120
%
66
PRT
22
OL Trip Time
60.0
sec
67
PRT
31
No Motor Trip
1
Free-Run
68
PRT
32
No Motor Level
5
%
69
PRT
33
No Motor Time
3.0
sec
70
PRT
40
ETH Trip Sel
1
Free-Run
71
PRT
41
Motor Cooling
0
Self-cool
72
PRT
42
ETH 1 min
115
%
73
PRT
43
ETH Cont
100
%
74
PRT
60
PipeBroken Sel
2
Free-Run
75
PRT
61
PipeBroken Lev
90.0
%
76
PRT
62
PipeBroken DT
10.0
sec
9.4.2.2 MC2 Fan Macro
The Fan Macro includes typical fan related parameter settings. Some of these are aSquared’ V/Hz
pattern for variable torque loads along with “S-Curve” acceleration and deceleration. A minimal DC Start is
set along with reverse run prevention. The shaded settings are different from the standard inverter
parameter settings.
MC2 ---> Fan
Macro
Group
Code
Related
Parameter
Code
Parameter Name
Setting
Value/Units
MC2
01
PRT
04
Load Duty
0
Normal
02
DRV
03
Acc Time
20.0
sec
03
DRV
04
Dec Time
30.0
sec
04
DRV
06
Cmd Source
1
Fx/Rx-1
05
DRV
07
Freq Ref Src
5
I2
06
DRV
09
Control Mode
0
V/Hz.
07
DRV
15
Torque Boost
0
Manual
08
DRV
16
Fwd Boost
2.0
%
09
DRV
17
Rev Boost
2.0
%
10
MOT
01
Motor Capacity
Defaults
11
MOT
02
Base Freq
60.00
Hz
12
MOT
03
Pole Number
4
Pole
13
MOT
04
Rated Slip
Defaults
14
MOT
05
Rated Curr
Defaults
15
MOT
06
NoloadCu rr
Defaults
16
BAS
07
V/F Pattern
1
Square
17
ADV
01
Acc Pattern
1
S-Curve
18
ADV
02
Dec Pattern
1
S-Curve
19
ADV
03
Acc S Start
40
%

Table of Contents