LCD Display Modes
290
890053-00-02
Warning
KPD H.O.A Lock
Buttons (HAND, OFF and AUTO) on
LCD - locked out with DRV-05
Lost Command
Command loss fault warning
Over Load
Overload warning
Under Load
Under load warning
Inv Over Load
Inverter overload warning
Fan Warning
Fan operation warning
DB Warn %ED
Braking resistor braking rate warning
Low Battery
Low battery warning
Check Line Plz
Connection or communication issue
between the LCD and the Control PCB.
Fire Mode
Fire mode warning
Pipe Broken
Pipe Break warning
Level Detect
Level detect warning
Lost Keypad
Lost keypad warning
Load Tune
Load curve tuning warning
Broken Belt
Broken belt warning
ParaWrite Fail
Smart copier error warning
Rs Tune Err
Auto tuning warning(Rs)
Lsig Tune Err
Auto tuning warning(Lsigma)
InFAN Warning
Inner Fan Warning 150~800HP
(110~500kW)
Note
Latch type fault: The inverter requires a manual reset.
Level type fault: The inverter will clear the fault when the condition is corrected or initialized.
Fatal type fault: There is no way to reset the fault other than cycling power to the inverter.