Communications
304
890053-00-02
seconds before the loss of the speed command and
uses it as the speed reference.
4
Hold Output
Operates continuously with the operate frequency
before the speed loss. The inverter calculates the
average output value for 10 seconds before the loss of
the speed command and uses it as the speed
reference.
5
Lost Preset
The inverter operates at the frequency set at PRT-14
(Lost Preset F).
PRT-14
Lost Preset F
0.00, Low Freq
High Freq
Set the frequency for continued operation.