Communications
312
890053-00-02
Comm.
Address
Parameter
Scale
Unit
R/W
Assigned Content by Bit
R/W
B5
Reserved
B4-B0
16:Emergency stop
8: W: Trip initialization
(01), R: Trip status
4: Reverse operation (R)
2: Forward operation (F)
0: Stop (S)
0h0007
Acceleration
time
0.1
sec
R/W
-
0h0008
Deceleration
time
0.1
sec
R/W
-
0h0009
Output
current
0.1
A
R
-
0h000A
Output
frequency
0.01
Hz
R
-
0h000B
Output
voltage
1
V
R
-
0h000C
DC link
voltage
1
V
R
-
0h000D
Output
power
0.1
kW
R
-
0h000E
Operation
status
-
-
R
B15
0: HAND, 1: AUTO
1: Frequency command
source by communication
(built-in, option)
B14
1: Operation command
source by communication
(built-in, option)
B13
B12
Reverse operation
command
B11
Forward operation command
B10
Reserved
B9
Jog mode
B8
Drive stopping
B7
DC Braking
B6
Speed reached
B5
Decelerating
B4
Accelerating
B3
Fault - operates according to
OUT-30 setting
B2
Operating in reverse
direction
B1
Operating in forward
direction
B0
Stopped

Table of Contents