Communications
327
890053-00-02
Group
Code
Name
LCD display
Parameter Setting
Setting Range
Unit
COM
03
Communication
Speed
Baudrate
9600 bps
0
1200
1)
1
2400
1)
2
4800
1)
3
9600
4
19200
5
38400
6
56Kbps
1)
7
76.8Kbps
8
115.2Kbps
1)
04
Communication
Mode
Int485 Mode
D8/PN/S1
0
D8/PN/S1
1
D8/PN/S2
2
D8/PE/S1
3
D8/PO/S1
20
Maximum
number of
BACnet Masters
BAC Max
Master
127
1127
-
21
BACnet device
number 1
BAC Dev Inst1
237
04194
-
22
BACnet device
number 2
BAC Dev Inst2
0
0999
-
23
BACnet device
password
BAC
PassWord
0
032767
-
1) 1200 bps, 2400 bps, 4800 bps, 56Kbps, 115.2Kbps cannot be set in communication speed
setting in case of BACnet communication.