Technical Specifications
365
890053-00-02
Items
Description
Frequency Limits
Jump Frequencies
Loss of Power
3-Wire Control
Ride Through (KEB)
Fire Mode
Safe Stop
Speed Search
V/Hz. Control Pattern
Linear, Squared, User V/Hz
Braking
Torque Boost
DC Injection Braking
Stall Prevention
Power Braking
Flux Braking
External Brake Control
H2 Pump Software
Lead/Lag and Alternating
Broken Pipe Detection
Jockey Pump Control
BACnet and Metasys-N2
MMC - Multi-Motor Control
Pump Load Tuning
Pre-Fill, Soft Fill
Decel Valve Ramp
Start and End Ramp
Time Event Scheduling
Backspin Timer
Flow Compensation
Pump Clean Operation
Energy Saving Operation
Input
Analog
(1) 010 V, (1) 0/420 mA, Switch selectable to 010 Vdc
Digital inputs
(7), Select PNP (Source) or NPN (Sink) mode. NO/NC selectable. Functions
of the digital inputs are set with parameters IN-65 through IN-71.
Functions
Forward/Reverse Operation
Reset
External Trip
Emergency Stop
Output Disable (Bx)
Jog
Fixed Speed - Step Freq's
Run Enable/Disable (Safety)
3-Wire Control Select
Damper Monitor and Control
2nd Source - HOA/LOR
Up/Down Operation
Analog Hold
PID Disable
Jog Start FWD/REV
Pre-Excite
Timer Input
Fire Mode
Event Timer
Pre-Heat
Pulse train
032 kHz, Low Level: 00.8 V, High Level: 3.512 V
Output
(1) Fault relay
(Form C)
N.O.: Less than AC 250 V, 2A, DC 30 V, 3A
N.C.: Less than AC 250 V, 1A, DC 30 V, 1A
(4)Programmable
relays (Form A)
N.O.: Less than AC 250 V, 5 A
Less than DC 30 V, 5 A
(1) open collector
terminal
Less than DC 26 V, 50 mA
(2) Analog
Outputs
AO1: 0(4) - 20 mA, Switch selectable to 010 Vdc
AO2: 0-10VDC
Frequency, Current, Voltage, Power, DC Bus Voltage, Fixed, more.
Pulse train
Maximum 32 kHz, 012 V

Table of Contents