Performing Basic Operations
68
890053-00-02
3.2.2.6 Switching between the HAND/OFF/AUTO Modes
Mode
Description
AUTO
HAN
D
Press the HAND button in AUTO mode to switch to HAND mode. The inverter
operates as follows based on the setting at DRV-26 (Hand Ref Mode).
Settings
Description
0
Hand
Parameter
The inverter operates based on the rotation
direction set at DRV-02 (Kepad Run Dir) and the
frequency reference set at DRV-25 (HAND Cmd
Freq).
1
Follow Auto
The inverter takes over the rotation direction and
the frequency reference from the settings for AUTO
mode and keeps performing the same operation. If
the inverter was stopped in AUTO mode, the
operation direction is set as Fx and the frequency
reference is set as 0 (no inverter output).
HAND
AUT
O
Press the AUTO button in HAND mode to switch to AUTO mode. The inverter
operates based on the command source and frequency reference settings set
at DRV-06 and DRV-07. If DRV-06 (Cmd Source) is set to ‘keypad’ press the
AUTO button once again to start inverter operation.
AUTOOFF
Press the OFF button in AUTO mode to stop the inverter operation (the
inverter enters OFF mode).
OFFAUTO
Press the AUTO button in OFF mode to switch to AUTO mode. The inverter
operates based on the command source and frequency reference settings
set at DRV-06 and DRV-07. If DRV-06 (Cmd Source) is set to ‘keypadpress
the AUTO button once again to start inverter operation.
HANDOFF
Press the OFF button in HAND mode to stop the inverter operation (the
inverter enters OFF mode).
OFFHAND
Press the HAND button in OFF mode to switch to HAND mode. The inverter
operates (Starts) based on the operation direction set at DRV-02 (Keypad
Run Dir) and the frequency reference set at DRV-25 (HAND Cmd Freq).