M-SV-001-EN Rev. G
3. Plug the connector of the new fan into the Soft Start Board. Refer to "Figure 4-117 Soft Start
Fan Connector".
J5 on the Closed-Top Soft Start
J3 on the Open-Top Soft Start
Figure 4-117 Soft Start Fan Connector
4. Install the top covers. Refer to "4.2 Compressor Covers" on page 56.
5. Return the compressor to normal operation.
4.15.10.1 Soft Start Torque Specifications
Table 4-26 Soft Start Torque Specifications
Description Nm Ft.Lb. In.Lb.
Soft Start fastener, M5x15 or M5x20 5 - 44
Soft Start Fan fastener, M5x35 - - 6
Upper Nut, 5/16" - 18 UNC 7 - 62
Jam Nut, 5/16" - 18 UNC 7 - 62
Lower Nut, 5/16" - 18 UNC 20 15 177
Cover fastener, M5x15 - - 13
4.16 SCR DC Bus Bar - TTS300/TGS230
The SCR DC Bus Bars pass the DC voltage from the output of the SCRs to the DC Capacitor Bus Bar
Assembly. This procedure does not show the removal of the Soft Start since it is not required. However,
if extra room is desired, the Soft Start can be removed to provide better access to the fasteners that
secure the SCR DC Bus Bars to the DC Capacitor Bus Bar Assembly.
Figure 4-118 SCR DC Bus Bars
J3 Connector
J5 Connector
Closed-Top Soft Start Open-Top Soft Start