4.23.6.1 Inverter Specific Removal Steps - TTS300/TGS230
1. Disconnect the two (2) SCR Gate connectors from each rectifier.
2. Remove the three (3) M6x16 fasteners that connect the Fast-Acting Fuses to the SCRs. Refer to
"Figure 4-198 Fuse Block Assemblies - TTS300/TGS230" for this and the following two (2) steps.
3. Remove the two (2) fasteners from each of the three (3) fuse block assemblies.
4. Remove the fuse assemblies along with the Mylar.
Figure 4-198 Fuse Block Assemblies - TTS300/TGS230
5. Remove the Terminal Block from the compressor.
Figure 4-199 Terminal Block Removal - TTS300/TGS230
AC Bus Bar to SCR
Fastener, M6x16
Fuse to Terminal
Block Fastener
SCR Gate
Connectors
(3 places)
Mylar
Terminal Block
Fastener, M5x15
(3 places)