The operator should avoid touching any components or connectors on the module and should hold
the module by its edge or enclosure, as applicable.
1.9.1 ESD Protection/Grounding
All parts that are susceptible to damage by ESD will be marked using the following label. Refer to
"Figure 1-8 ESD Label". Please follow the instructions below to ensure safety and to protect the parts
from ESD damage.
Figure 1-8 ESD Label
1. Isolate the compressor power as described in "1.8 Electrical Isolation" on page 19.
2. Remove the Mains Cover. Refer to "4.2.1 Mains Input Cover" on page 56.
3. Clip the ESD strap ground clip to the compressor ground post. Refer to "Figure 1-9 Mains Plate
and Ground Post".
Figure 1-9 Mains Plate and Ground Post
4. If you need to remove the Soft Start, clip the ESD strap ground clip to the mains plate. Refer to
"Figure 1-9 Mains Plate and Ground Post".
5. If you only need to remove the Service Side Cover, clip the ESD strap ground clip to the cover
screw hole that is part of the compressor housing. Refer to "Figure 1-10 Compressor Grounding
Points".
Figure 1-10 Compressor Grounding Points
Mains Plate
Ground Post
Ground Points