166 of 282 M-SV-001-EN Rev. G
phase 1 AC terminal and the black (-) multimeter lead on the DC+ terminal. The measured
value should be 0.275V – 0.4V. Refer to "Figure 4-193 Inverter Diode Measurements (Skiip 613
Shown)" for this and the following three (3) steps.
7. Keeping the red (+) multimeter lead on the phase 1 AC terminal, place the black (-) multimeter
lead on the DC- terminal. The measured value should be open.
8. Place the black (-) multimeter lead on the phase 1 AC terminal and the red (+) multimeter lead
on the DC+ terminal and record the results. The measured value should be open.
9. Keeping the black (-) multimeter lead on the phase 1 AC terminal, place the red (+) multimeter
lead on the DC- terminal. The measured value should be 0.275V – 0.4V.
10. Repeat Steps 6 through 9 for the remaining Inverter phases.
Figure 4-193 Inverter Diode Measurements (Skiip 613 Shown)
4.23.3 Inverter Cable Harness
Figure 4-194 Inverter Cable Harness
4.23.4 Inverter Cable Harness Removal and Installation
4.23.4.1 Inverter Cable Harness Removal
1. Isolate the compressor power as described in Section "1.8 Electrical Isolation" on page 19.
2. Remove the Service Side Cover. Refer to "4.2.3.1 Service Side Cover Removal and Installation"
on page 58.
3. Remove the Soft Start. Refer to "4.15.3 Soft Start Removal and Installation" on page 112.
NOTE
These values can vary depending on the meter being used. The main idea is that the values be consistent between phases.
AC Output Phases
1
2
3
DC Input
+
+
+
-
-
-