M-SV-001-EN Rev. G
Figure 4-66 Locking Collar Installation
11. Rotate the worm gear by hand until the set screw hole in the worm gear is visible through the
access hole in the casting. Verify that the worm gear turns freely. Do not install the set screw at
this time. Refer to "Figure 4-67 IGV Worm Gear Alignment".
Figure 4-67 IGV Worm Gear Alignment
12. Insert the IGV Motor wires through the Feed Through hole.
13. Check the position of the flat surface of the shaft relative to the locating pin. The flat surface
should be oriented facing up, ready to be inserted in the worm gear. Refer to "Figure 4-68 Shaft
Position".
Figure 4-68 Shaft Position
14. Install the motor into the housing and align the motor shaft flat surface with worm gear
adapter.
15. Ensure the motor locating pin is aligned with the notch in the housing flange. Refer to "Figure
4-69 IGV Motor Alignment" on page 90.
Drive Pin Holes
Locking Collar
Worm Gear
Aligned
Flat surface of the
shaft facing UP
Check locating
pin position
• • • CAUTION • • •
Check that wiring is clear of housing and edges of motor.

Table of Contents

Other manuals for Danfoss Turbocor TTS Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss Turbocor TTS Series and is the answer not in the manual?

Danfoss Turbocor TTS Series Specifications

General IconGeneral
BrandDanfoss
ModelTurbocor TTS Series
CategoryCompressor
LanguageEnglish

Related product manuals