EasyManua.ls Logo

Danfoss Turbocor TTS Series

Danfoss Turbocor TTS Series
282 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
249 of 282
M-SV-001-EN Rev. G
Motor Fault
Descritpion
Trigger
Method
Troubleshooting
DC Bus Under/Over
Voltage Fault
DFT At 0 RPM: If the measured DC Bus voltage is lower than Soft Start charge voltage, a DC bus voltage fault is
recorded. All 3-phase voltage information displayed in the SMT is calculated from DC bus voltage, as measured by
the Inverter.
Typically, this fault is recorded when power to the compressor is removed.
Measure the incoming main AC voltage.
Compare the measured voltages to the displayed readings in the Compressor Monitor Tool and Fault and Event
Log details to determine conditions related to the fault.
Measure the DC bus voltage using the DC Bus Test Harness. Refer to "1.10.1 General Verification and Installation of
the DC Bus Test Harness" on page 22.
Verify the Soft Start. Refer to "4.15.2 Soft Start Verification" on page 109.
Verify the SCRs. Refer to "4.19.2 SCR Verification" on page 135.
Verify the connections to the Inverter. Refer to "4.23.2.1 Inverter Verification" on page 165.
24VDC Under/Over
Voltage Fault
RFT Suggests the measured 24VDC supply voltage is out of range.
Measure the 24VDC test points at the Backplane. Refer to "4.26.2.2 Backplane Verification" on page 210.
Compare the measured voltages to the displayed readings in the Compressor Monitor Tool and Fault and Event
Log details to determine conditions related to the fault.
If the measured voltage is incorrect, verify the DC-DC Converter. Refer to "4.25.2 DC-DC Converter Verification" on
page 201.
Determine that one of the modules is not draining energy. Refer to "5.5.2 Determining the Cause of an Energy
Drain" on page 257.
If the fault occurs when the compressor is given the demand to run, the Inverter may be causing the 24VDC fault.
Low Motor Back
EMF
Fault
DFT The calculated magnetic strength of the shaft has fallen below the minimum limit. This can be a temporary effect
due to high load and elevated temperatures (will recover when cavity temperature cools) or due to a permanent
demagnetization of the shaft.
If this fault occurs three times within a 30-minute period, a Lock-Out Fault will occur.
Compare the Back EMF value to the displayed readings in the Compressor Monitor Tool and Fault and Event Log
details to determine conditions related to the fault.
Permanent damage to Back EMF can be caused by insufficient motor cooling, repeated overheating of cavity,
faulty Inverter, faulty BMCC, repeated Rotor May Be Locked or Single phase Over-Current faults. See Inverter Error.
Verify the Inverter. Refer to "4.23.2.1 Inverter Verification" on page 165.
Verify the Stator. Refer to "4.24.4 Motor Verification" on page 192.
Generator Mode
Active
DFT Indicates, at greater than 0 RPM, the measured actual DC Bus voltage has fallen below the Generator Mode
Enabled Level value. Also, could be electronic “noise when no actual drop in voltage has occurred.
Measure the incoming main AC voltage.
Measure the DC bus voltage using the DC Bus Test Harness.
Compare the measured voltages to the displayed readings in the Compressor Monitor Tool and Fault and Event Log
details to determine conditions related to the fault.
Typically, this fault is recorded when power to the compressor is removed while it is running.
EEPROM Checksum
Fault
INS Indicates there is an error reading the EEPROM in the BMCC.
Perform a bearing calibration and save to EEPROM, cycle the power.
If the error is still present, the BMCC must be replaced.
SCR Ripple Voltage
Fault
AFT Indicates that a voltage imbalance may exist between the incoming AC phases.
Measure the difference in current and voltage between the phases.
If there is a current imbalance (more than 5%) between the phases, verify the incoming AC power supply.
Review the Compressor Monitor Tool for SCR Voltage Ripple readings at the time of the fault.
Phase imbalance can be caused by a faulty SCR, SCR Gate, Gate control from the Soft Start Board, or a faulty power
capacitor.
Verify the SCRs. Refer to "4.19.2 SCR Verification" on page 135.
Verify the Soft Start Board. Refer to "4.15.2 Soft Start Verification" on page 109.

Table of Contents

Other manuals for Danfoss Turbocor TTS Series

Related product manuals