Figure B-22 Compressor Voltage Troubleshooting Flowchart (Sheet 1)
Start
Allthreephasesofvoltage
presentaftermainsfuses?
Carefullyremove
MainsInputCover
Withanappropriatelyrated
meter,verifyall3phasesof
voltagebeforethemains
fuses
Verifyand,if
needed,replace
FusesReferto
TerminalBlockFuse
Replacement4.3
Electricallyisolate
compressorRefer
toElectricalIsolation
1.7
Yes
No
RemovetheTop
Cover
Inspectall
electronicsfor
visibledamage
Arethereanysigns
ofvisibledamage?
VerifySoftStart
fuses(ClosedTop
SoftStartOnly)
No
Replacedamaged
components
AretheSoftStart
fuseswithin
specification?
Replacefuseand
refertoDetermining
theCauseofthe
BlownFuse5.5.2.6
No
VerifyIGBTcableto
theIGBTconnectors
areinstalled
correctly
Yes
VerifyDCDC
resistances
Areresistances
correct?
No
ReplaceDCDCand
verifyPWMand
bearingsReferto
PWMVerification
4.27.3
Yes
Yes
A
End