031914 M4-75
XS5 INFEED HOUSING MANIFOLD NODE: The Main
Profibus Cable travels from the XS4 Scale Housing
Manifold to the “In” Port on the XS5 Infeed Housing
Manifold. There is a “Terminating Resistor” installed on
the “Out” Port to the XS5 Infeed Housing Manifold.
(Illustration 146) The XS5 Infeed Housing Manifold
receives Input Signals from the Loaf Gate Position
proximities. The XS5 Manifold also receives control
signals from the Computer to energize the directional
valves that operate the Loaf Gate air cylinders, open and
close the Grippers and raise and lower the Loaf Tray.
1. When all “Safety” conditions have been met, the
KA1/KA2 Relay energizes and sends 24 VDC
Control Voltage on wires 9 and common (2) to
pins 2 and 3 on the Power Cable Connector of
the XS5 Infeed Housing Manifold Node.
(Illustration 146) This voltage is used to operate
the XS5 Node. If a guard is “opened, the
KA1/KA2 Relay will de-energize and there will be
no voltage to operate the XS5 Node.
2. The GS1 Power Supply sends 24 VDC Control
Voltage through the QF4 Circuit Breaker on wires
7 and common (2) to pins 1 and 3 on the Power
Cable Connector of the XS5 Infeed Housing
Manifold Node. This voltage is used to operate
the components controlled by the XS5 Node.
3. There must be a Terminating Resistor installed in
the “Out” Port of the XS5 Node.
4. The Address Setting for the XS5 Node must be
set correctly in order for the Node to operate.
(Illustration 147)
IMPORTANT!
When replacing any of the Remote Nodes, the
“address setting” must be set correctly or the
Remote Node will not operate correctly! There will be
“NO” Profibus Communication between the
Computer and the Node. Refer to the “Profibus
Routing and Address Information” page of the
schematic for the correct address for each Node.
ILLUSTRATION 147
ILLUSTRATION 146
XS5 INFEED HOUSING MANIFOLD
TERMINATING RESISTOR