NO TE
1. The ECC800-Pro supports only SMS notication service but not data service by
using the 4G module.
2. China: 2G and 4G networks support China Unicom or China Mobile SIM cards, and
3G networks support only China Unicom SIM cards.
3. Outside China: Select SIM cards according to the following wireless modes and
frequency bands:
4G: wireless mode (FDD-LTE and TDD-LTE), coverage frequency band (B1, B3,
B5, B7, B8, and B20)
3G: wireless mode (WCDMA), coverage frequency bands (B38, B40, and B41)
2G: wireless mode (GSM), coverage frequency band (900/1800 MHz)
The ECC800-Pro is connected to a network with an email server through a
WAN port. Both the Internet and local area network (LAN) are supported.
Procedure
Step 1 Choose System Settings > Event Notication.
Step 2 Set related outbox parameters.
1. Set related parameters in the Outbox Settings area on the Mailbox Settings
page. If the address type of the outbox is Domain name, choose System
Settings > System Parameters, and set related parameters in the DNS
Server Address area on the Monitor IP page.
NO TE
The DNS server address is provided by the local network operator.
2. Click Test to check the email sending. If an email fails to be sent, check the
outbox settings and DNS Server Address. If the email is sent successfully,
click Submit.
NO TICE
If Test email sending failed is displayed, check whether the receiver's email
server requires CA
certicate verication. If it is required, download the CA
certicate from the receiver's email website and upload it in the Mailbox
Certicate area.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 5 Power-On Commissioning
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 108