The settings in the following table are used as examples to describe the basic conguration.
Table 6-44 Basic conguration
Parameter Setting Description
Device Name IT Cabinet 101 Set based on the actual device
name.
Cabinet height 42 U space quantity of the
cabinet.
Cabinet width 600 The width of the cabinet.
Power
Distri
butio
n
Para
meter
Settin
gs
Power
syste
m
Single-phase Set single-phase or three-
phase based on the actual
power supply.
Numb
er of
power
suppli
es
2 rPDU quantity.
Rated
cabin
et
power
6.00 Set based on the actual rated
power of the cabinet.
rPDU-A01 PDU80001 > 1QF1(L1) Select a power distribution
device and power distribution
branch for the rPDU
numbered rPDU-A01 in the
cabinet.
rPDU-B01 PDU80001 > 2QF1(L1) Select a power distribution
device and power distribution
branch for the rPDU
numbered rPDU-B01 in the
cabinet.
ECC800 Data Center Controller
User Manual (for ECC800-Pro) 6 Feature Description
Issue 02 (2020-09-07) Copyright © Huawei Technologies Co., Ltd. 219