363-206-204
Release 8 Installation Tests
Issue 9 October 1998
7-17
7. Change the DS3 violation monitoring mode back to VMR at the CO and RT,
using the set-t3 command.
8. Repeat the procedure for each function group equipped with DS3 packs.
9. After completion of DS3 testing, release the DS3 loopbacks at the RT by
performing the following:
a. Issue the command rls-lpbk-t3 or rls-lpbk-ec1;
b. At the address prompt, enter fn-all
c. At the execute prompt, enter Y
d. Verify loopbacks are no longer present by entering rtrv-alm
10. Remove all test signals from the DDM-2000 OC-3.
11. Press the UPD pushbutton on the SYSCTL.
Final Operations
Procedure
1. Verify that all test signals and loopbacks from the DDM-2000 OC-3 have
been removed.
2. Press the UPD pushbutton on the SYSCTL.
3. Verify that the system is configured for normal operation and that no alarms
are present (other than the BBG6 alarms described previously). If alarms
are present, refer to the "Troubleshooting" section of this manual.
4. Connect the office alarm cables if they have been disconnected.