29.5 Precautions
29.5.1 Precautions common to each software
29 - 21
25
BAR CODE READER
CONNECTION
26
PRINTER CONNECTION
27
CNC CONNECTION
28
MULTI-CHANNEL
FUNCTION
29
FA TRANSPARENT
FUNCTION
30
MULTIPLE-GT11
CONNECTION FUNCTION
31
GATEWAY FUNCTION INDEX
5 When the FA transparent function is used in a bus connection
(1) When GOT monitoring is faulty
The FA transparent function cannot be used in case that the GOT monitoring is faulty due to PLC
CPU errors or faulty communication between the PLC CPU and GOT.
When GOT monitoring is faulty, check the following.
(2) When mutiple GOTs are bus-connected
When multiple GOTs are bus-connected, the FA transparent function can be used on each GOT.
However, note that the monitoring performance of each GOT slows down as the number of
monitoring GOTs and PCs increases.
(3) When the FA transparent function is used in a bus connection
When the FA transparent function is used in a bus connection, the following GX Developer
functions cannot be executed.
The message "The executed function is not supported. Please check the manual and other
documentation." is displayed on GX Developer
1 Whether the PLC CPU operates normally
Refer to the User's Manual of the PLC CPU you use.
2 Whether the PLC CPU and GOT are connected normally
• Chapter 2 BUS CONNECTION
• Chapter 3 DIRECT CONNECTION TO CPU
Unsupported GX Developer functions Remarks
Remote Reset
Remote system reset
Remote RUN
Remote STOP
Remote PAUSE
Remote STEP-RUN
Remote latch clear
Write clock data
Clear malfunction log
Inexecutable only when specify all stations/groups has been
performed.
PC
RS-232
Cable