5.4 Precautions
1 Network configuration
Use MELSECNET/10 (PLC to PLC network) to configure a network including the GOT.
The following networks including the GOT cannot be configured.
• MELSECNET/10 (Remote I/O network)
• MELSECNET/H (PLC to PLC network: MELSECNET/H Mode, MELSECNET/H Extended Mode)
• MELSECNET/H (Remote I/O network)
2 Monitoring range
Only PLC CPU of the same networks No. can be monitored in GOT.
For details, refer to the following manual.
GT Designer2 Version Screen Design Manual
3 Connecting to QCPU (Q mode)
Use function version B or later of the MELSECNET/H network module and QCPU (Q mode).