22 - 20
22.3 Preparatory Procedures for Monitoring
22.3.3 Setting communication interface (Communication settings)
2 Communication detail settings
Item Description Range
Transmission Speed
Set this item when change the transmission speed used for
communication with the connected equipment.
<Default: 9600bps>
9600bps,19200bps,38400bps,
57600bps,115200bps
Data Bit
Set this item when change the data length used for communi-
cation with the connected equipment.
<Default: 8bit>
7bit/8bit
Stop Bit
Specify the stop bit length for communications.
<Default: 1bit>
1bit/2bit
Parity
Specify whether or not to perform a parity check, and how it is
performed during communication.
<Default: None>
None
Even
Odd
Retry
Set the number of retries to be performed when a
communication error occurs.
<Default: 0 Times>
0 to 5 Times
Timeout Time
Set the time period for a communication to time out.
<Default: 3 Sec>
3 to 30 Sec
Delay Time
Set this item to adjust the transmission timing of the
communication request from the GOT.
<Default: 0ms>
0 to 300 ms

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Mitsubishi GOT1000 Series and is the answer not in the manual?

Mitsubishi GOT1000 Series Specifications

General IconGeneral
Power Supply24 VDC
TypeHMI (Human Machine Interface)
SeriesGOT1000
Resolution640 x 480 pixels
Touch Panel TypeResistive
InterfaceRS-232, USB
Storage Temperature-20 to 60°C
Protection RatingIP65
Display TypeTFT LCD
Brightness400 cd/m²
Backlight Life50, 000 hours
CPURISC
Shock Resistance147 m/s²
Display Size10.4 inches