5 Use of the Commissioning Tools
- 101 -
5
F8: test function
After you enter the F8 menu, the 7-segment LEDs display "0". The setting of F8 is described as
follows:
1: Hall call forbidden
2: Door open forbidden
3: Overload forbidden
4: Limit switches disabled
6: Entering slip experiment state
After the setting is complete, press the SET button. Then the 7-segment LEDs display "E88" and
blink, prompting that the elevator is being tested. When you press PRG to exit, F8 is back to 0
automatically.
F9: reserved
FA: auto-tuning
After you enter the FA menu, the 7-segment LEDs display "0". The setting range of FA is 1 and 2,
as follows:
1: With-load auto-tuning
2: No-load auto-tuning
After the setting is complete, press the SET button. Then the 7-segment LEDs display "TUNE",
and the elevator enters the auto-tuning state.
After conrming that the elevator meets the safe running conditions, press the SET button again
to start auto-tuning.
After auto-tuning is complete, the 7-segment LEDs display the present angle for 2s, and then
switch over to the F0 menu.
You can press the PRG button to exit the auto-tuning state.
Fb: CTB state display
After you enter the Fb menu, the 7-segment LEDs display the input/output state of the CTB. The
following gure shows the meaning of each segment of the LEDs.