5 Use of the Commissioning Tools NICE3000
new
User Manual
- 106 -
5
Press
PRG
from a Level III menu to:
Return to the Level II menu without saving the parameter value, and remain at the current function
code.
Unchangeable Parameters
When operating in Level III menus, if the parameter does not include a blinking digit, then it is not
allowed to change that parameter. There are two possible reasons for this:
1) The function parameter you have selected is read-only. This is because:
The display is showing the controller model.
The display is showing an actual parameter detected by the system.
The display is showing a running record parameter.
2) The displayed function parameter cannot be changed while the controller is in the RUN state. You
can change these types of parameter only when the controller is in the stop state.
2. Viewing and modifying function codes in bit
F5-33
Decimal value
00000
00000
Binary value
04000 04001
...
05000
15000
ENTER
ENTER
PRG
04000
3. Viewing modied parameters
Function Code Parameter Name Setting Range
FP-02 User-dened parameter display
0: Invalid (Default)
1: Valid
You can view the user-modied parameters.
Set FP-02 to 1, and the operation panel displays only the parameters that are different from the
default setting.
If you want the operation panel to display all parameters, restore FP-02 to the default value 0.